Base Technology |
Dual Flash based Processors with Real Time Clock, Trace diagnostics, PuLsE communications & programmable languages |
Display |
Backlit 240 x 64 Graphical Display |
LED Indicators |
3 Red (2 x Fire, 1 x Alarm), 1 Green (Power) & 12 Amber (Fault & System) |
Controls |
Alpha Numeric Keypad, Navigation Keys & System Keys for Reset, Mute, Silence/Resound & Evacuate |
Protocols |
Hochiki ESP, Apollo XP95 and Discovery |
Number of Fire Zones |
100 'Dynamix' |
Number of Loops |
1-2. Expandable via individual plug-in loop driver |
Devices per Loop |
As per Detector Manufacturer's Specifications |
Loop Current |
500 mA Tools |
On Board Sounder Circuits |
2 x 1 Amp programmable |
On Board Relays |
2 x 1 Amp 30V AC/DC Programmable |
Auxiliary Supply |
1 x 24V 300mA Switchable |
Open Collector / Logic Outputs |
8 x Programmable |
Programmable Switch Inputs |
8 Volt Free Digital Inputs with flexible programming |
On Board Power Supply |
3 Amp High Efficiency Switched Mode |
Mains Supply |
220V - 240 V 50 Hz AC (+10%, -15% tolerance) |
Battery Capacity |
24V 18Ah internal. 24V 48Ah large enclosure. |
Charger Current |
2 Amp DDP monitored, temperature compensated internal charger |
Serial Ports |
1 RS232 Onboard for PC, Modem or Dedicated Printer |
Programming |
Via on-board Keypad or PC running Windows Tools |
Event Log |
1000 Fire & Event + Diagnostic |
Networking |
Optional plug in card |
Printer (Option) |
Dedicated port for optional integral serial printer |
Enclosure |
Steel IP30 |
Cable Entry |
20mm Knock-outs. 18 x top, 9 x top rear and 2 bottom |
Colour |
Beige (textured) |
Dimensions H x W x D mm |
475 x 450x 115 |
Weight |
10.5Kg |
Metalwork Options |
Flushing Bezel, Ancilliary Enclosure and Battery Box |
Standards |
Designed to comply with EN54 parts 2/4 |